EN
2026Nov 4

Voltage Drop and Cable Sizing: Reading Japanese Formulas

Drawings & SpecsUpdated November 4, 202619 min read

A Japanese contractor sends the cable calculation sheet for a new production line. One column is headed 電圧降下 (den'atsu koka, "voltage drop"), and every row uses the same formula: e = 30.8 × L × I ÷ (1000 × A). The cables are 5.5, 8, and 14 mm², each circuit is marked "2% or less," and your project specification cites the NEC or IEC 60364.

The numbers are not mysterious. The coefficients 35.6, 30.8, and 17.8 come from the resistance of copper wire, and the 2% limit comes from a Japanese wiring code. Once you know the assumptions behind them, you can check the sheet against your own method and limits.

This guide explains what voltage drop is and why it matters, how to read the Japanese simplified formula, how it lines up with NEC and IEC practice, how Japanese cable sizes compare with IEC and AWG sizes, and what to ask the Japanese side before you accept a cable size. Final design decisions belong to a qualified engineer working to the codes that apply at your site.

Contents
  1. What Is Voltage Drop?
  2. Four Factors That Increase Voltage Drop
  3. Equipment Problems Caused by Voltage Drop
  4. How to Read the Japanese Simplified Formula
  5. Japanese Formula vs. NEC and IEC Methods
  6. Allowable Voltage Drop: Japan vs. IEC vs. NEC
  7. Cable Sizes: Japanese mm², IEC mm², and AWG
  8. How a Japanese Sizing Sheet Is Usually Built
  9. Ways to Reduce Voltage Drop
  10. Checklist: Reviewing a Japanese Voltage Drop Calculation
  11. Questions to Ask the Japanese Side
  12. Where This Guide Does Not Apply
  13. Frequently Asked Questions
  14. Sources

What Is Voltage Drop?

Cross-sections of three-core power cables of different sizes showing stranded copper conductors

Even copper and aluminum conductors have some resistance. When current flows, Ohm's law says a voltage equal to current × conductor resistance is used up along the cable, so the voltage at the load terminals is lower than at the source.

A Japanese government technical reference on electrical installations (Ministry of Agriculture, Forestry and Fisheries) defines voltage drop as the fall in voltage between the supply point and the point of use, caused by conductor resistance and reactance. Reactance is the property that opposes changes in current in an AC circuit.

The lost voltage multiplied by the current turns into heat in the cable. That heat is wiring loss.

Figure 1: How Voltage Falls Between the Source and the Load

Current flows out on one conductor and back on the other, and each conductor's resistance uses up a little voltage.

Source 200 VConductor resistanceCurrent IDrop in both conductorsLost voltage becomes heatLoad ≈ 196 V

Example values for a 2% (4 V) drop. In three-phase circuits, the number of conductors and the coefficient change (see Figure 5).

The same thing happens with a long extension cord. Hataya, a Japanese extension cord maker, gives an example in which 5 A through a 20 m cord with 0.75 mm² conductors drops about 4.7 V, so 100 V at the outlet becomes about 95.3 V at the far end.

Four Factors That Increase Voltage Drop

Voltage drop is the product of conductor resistance and current. Resistance rises as a cable gets longer and thinner, and AC circuits add reactance and power factor, so the causes fall into four groups.

Figure 2: Four Factors That Increase Voltage Drop

If any one of them gets worse, the voltage reaching the load falls.

Long runResistance is proportional to length, out and back
Small conductorResistance is inversely proportional to cross-section
High currentAdded loads, or motor starting
Power factor and reactanceGrows when AC current lags the voltage

The Ministry of Agriculture, Forestry and Fisheries reference lists the causes as resistance, reactance, current, and power factor.

Longer, Smaller Conductors Have More Resistance

Conductor resistance is proportional to length and inversely proportional to cross-sectional area. Doubling the length doubles the resistance, and so does halving the area, so the farther the load and the smaller the cable, the larger the drop.

A Japanese catalog for 600 V CV cable (XLPE-insulated, PVC-sheathed power cable) shows the scale. For three-core cable, the maximum conductor resistance at 20°C (68°F) is 2.36 Ω/km for 8 mm² and 1.34 Ω/km for 14 mm². Going up one size cuts the resistance to about 60%.

Higher Current Means a Larger Drop

On the same cable, doubling the current doubles the voltage drop. That is why a circuit that worked fine can start showing low voltage after new equipment is added to it.

Motor starting needs special attention, because a squirrel-cage induction motor draws a large current for a short time when it starts. Japanese references call this 瞬時電圧降下 (shunji den'atsu koka, momentary voltage drop) and treat it separately from the steady-state drop during normal running.

Power Factor and Reactance Also Matter

In AC wiring, reactance lowers the voltage along with resistance. With loads such as motors, where the current lags the voltage, the reactive component adds to the drop. The same current can therefore cause a larger drop than it would in a DC circuit.

Larger cables have lower resistance, but their reactance falls much less. On large feeders, power factor therefore has a noticeable effect.

Equipment Problems Caused by Voltage Drop

Maintenance technician checking a motor terminal box with a clamp meter

When the terminal voltage falls, equipment cannot deliver its rated performance. The Ministry of Agriculture, Forestry and Fisheries reference lists the effects by equipment type. The ones most relevant to factories are shown below.

Figure 3: Common Problems Caused by Voltage Drop

Equipment stopping, motors failing to turn, and flickering lights are the symptoms people notice first.

Induction motorsTorque falls and current rises. A heavily loaded motor may fail to start
ComputersCan stop or malfunction. Electronics sensitive to low supply voltage are most at risk
LightingFlicker or lamps going out, so the light level in the work area becomes unstable
Nearby customersA large motor's starting current can pull down the distribution line voltage for others

Based on Table 7.1-8 in the Ministry of Agriculture, Forestry and Fisheries reference (in Japanese).

Motors are particularly affected. Oriental Motor explains that motor torque is approximately proportional to the square of the input voltage. By that relationship, a 10% voltage drop leaves only about 81% of the torque, so a heavily loaded machine may not reach speed and will draw more current.

The Utility Supply Voltage in Japan Also Varies

If the equipment will run in Japan, start from the utility voltage. Under Article 26 of the Electricity Business Act and Article 38 of its Enforcement Regulation, utilities must keep low-voltage supply within 101 V ±6 V on 100 V systems and 202 V ±20 V on 200 V systems. On a 200 V system, the voltage at the supply point can therefore be as low as 182 V.

The drop inside the plant comes on top of that. At a plant where the incoming voltage runs low, a long cable can push the terminal voltage below what the equipment accepts, so look at both together.

Steady-State Drop, Starting Dip, and Flicker

When voltage drop is suspected, the timing of the dip is the first clue. Low voltage all through operation points to cable length or size, a dip only at start-up points to starting current, and short repeating swings point to flicker (frequent voltage fluctuation that makes lights flicker).

Figure 4: Narrowing Down the Cause From the Symptom

Compare the voltage at the supply end and at the load at the same time, then sort by when the difference appears.

Compare voltage at both ends of the cableFor example, at the panel outgoing terminals and at the equipment terminals
When does the difference appear?
Throughout operationSteady-state drop. Review cable length, size, and load current
Only at start-upMomentary drop. Check starting current and starting method
Repeating at short intervalsFlicker. Identify the fluctuating load; involve the utility if needed

If the incoming voltage itself is low, the cause may be on the utility side rather than in the plant wiring. Measurements on live equipment should be made by qualified personnel under site safety rules.

For momentary dips at start-up, a starting method that limits inrush current helps.

How to Read the Japanese Simplified Formula

Japanese calculation sheets use one of two formulas: a 簡易式 (kan'i-shiki, simplified formula) for quick estimates, and a 基本式 (kihon-shiki, basic formula) that includes power factor and reactance. In practice, the simplified formula is used to estimate branch circuits, and the basic formula is used for a closer look at large feeders and motor loads.

The Coefficient Depends on the Wiring System

In a single-phase 2-wire circuit, current flows out on one conductor and back on the other, so the drop is twice the drop in one conductor. In a three-phase 3-wire circuit, the drop is measured line to line, so the factor is √3 (about 1.73).

Japan also uses single-phase 3-wire systems that carry 100 V and 200 V on one set of conductors, similar to North American 120/240 V split-phase service. Between a line conductor and the neutral, the factor is 1, because no current flows in the neutral when the loads are balanced.

Figure 5: Voltage Drop Formulas by Wiring System

The coefficient changes with the system, and the numbers in the simplified formula follow from it.

Single-phase 2-wire
(単相2線式)
Single-phase 3-wire
(単相3線式)
Three-phase 3-wire
(三相3線式)
Typical use in Japan
100 V outlet and lighting branch circuits
Feeders carrying 100 V and 200 V together
200 V and 400 V motors and other power loads
Drop measured between
The two conductors
Line and neutral
Two lines (line-to-line voltage)
Coefficient K (basic formula)
2 (out and back)
1 (no neutral current)
√3 (about 1.73)
Simplified formula
e = 35.6 × L × I ÷ (1000 × A)
e = 17.8 × L × I ÷ (1000 × A)
e = 30.8 × L × I ÷ (1000 × A)

e: voltage drop [V]; L: route length, one way (こう長, kocho) [m]; I: current [A]; A: conductor cross-section [mm²]. The simplified formula assumes copper at 97% conductivity, power factor 1, no reactance, the load concentrated at the far end, and balanced phases (three-phase and single-phase 3-wire). Basic formula: e = K × I × (R cos θ + X sin θ) × L, with R and X per km and L in km.

Where 17.8, 35.6, and 30.8 Come From

The 17.8 is the resistance, in ohms, of 1 km of 1 mm² copper conductor at 97% conductivity. Annealed copper at 100% IACS (International Annealed Copper Standard) has a resistivity of 1/58 Ω·mm²/m at 20°C. Dividing by 0.97 gives about 0.0178 Ω·mm²/m, or 17.8 Ω per km for 1 mm².

Multiply 17.8 by the single-phase factor of 2 and you get 35.6. Multiply it by √3 and you get 30.8. Each formula is simply "resistance of one conductor × coefficient × current," rewritten.

L Is the One-Way Length

Japanese sheets label the length こう長 (kocho), the one-way route length from the source to the load. The return path is already built into the coefficient. Entering the round-trip length doubles the result and leads to an oversized cable.

The US K-factor formula works the same way: its L is also the one-way length, and the factor of 2 or 1.732 covers the return path.

Assumptions Behind the Simplified Formula

The simplified formula assumes power factor 1 and ignores reactance. On large feeders that mainly supply motors, it gives a lower value than the actual drop. One Japanese electrical supplier's guide notes that the simplified formula can come out about 20% lower than the basic formula and recommends the basic formula for feeders.

The basic formula uses the AC conductor resistance R and reactance X per km from the cable manufacturer's catalog, plus the load power factor cos θ. Typical power factors used are 0.8–1.0 for lighting and about 0.75–0.8 for motor loads. When loads are tapped off along the run, each section is calculated separately and the results are added.

Japanese Formula vs. NEC and IEC Methods

The three methods share the same physics: current × resistance (plus reactance) × a coefficient for the wiring system. They differ mainly in units, conductor temperature, and how the resistance figure is chosen.

Figure 6: Three Common Ways to Calculate Voltage Drop

Same structure, different units and resistance basis.

Japanese simplified formula
US K-factor formula
IEC 60364-5-52 Annex G
Form
e = 30.8 × L × I ÷ (1000 × A) (three-phase)
VD = 1.732 × K × I × L ÷ CM (three-phase)
Coefficient b × (resistance × cos φ + reactance × sin φ) × current
Units
L in m, A in mm²
L in ft, CM in circular mils
Metric (m, mm²)
Resistance basis
Copper at 97% conductivity, 20°C (17.8 Ω·mm²/km)
K = 12.9 for copper (21.2 for aluminum), from NEC Chapter 9, Table 8 at 75°C
Resistivity value set in the standard; check the edition you use
Reactance
Ignored (power factor 1)
Ignored (DC resistance)
Included

Converted to metric units, K = 12.9 Ω·cmil/ft is about 21.4 Ω·mm²/km, roughly 20% higher than the 17.8 used in the Japanese formula. For the same circuit, the US formula therefore gives a larger drop.

That difference matters when you compare results. A Japanese sheet that shows a circuit just inside 2% may land at or slightly above that limit when you recalculate it with a 75°C resistance. Neither result is wrong; they are based on different conductor temperatures.

Advertisement

Allowable Voltage Drop: Japan vs. IEC vs. NEC

In Japan, the usual reference for low-voltage wiring is the 内線規程 (Naisen Kitei), the Japan Electric Association's indoor wiring code, JEAC 8001, Section 1310. The basic rule is 2% or less of the standard voltage for the feeder and 2% or less for the branch circuit. Where the supply comes from a transformer on the premises, the feeder may be up to 3%.

For long runs, the code allows a larger combined figure for feeder plus branch circuit, depending on the route length from the transformer secondary terminals or the service entrance to the farthest load. Japanese cable suppliers quote the values from Section 1310 as follows.

Route length to the farthest loadSupplied from a transformer on the premisesSupplied at low voltage by the utility
60 m (197 ft) or lessFeeder ≤3%, branch circuit ≤2%Feeder ≤2%, branch circuit ≤2%
Over 60 m up to 120 m (394 ft)Total ≤5%Total ≤4%
Over 120 m up to 200 m (656 ft)Total ≤6%Total ≤5%
Over 200 mTotal ≤7%Total ≤6%
Source: Taiyo Cabletec and Denzai Land, both quoting JEAC 8001 Section 1310 (in Japanese)

Here, the 幹線 (kansen, feeder) runs from the service entrance to the main distribution board for a low-voltage supply, or from the transformer secondary terminals to the board for a high-voltage supply. The 分岐回路 (bunki kairo, branch circuit) runs from the breaker in the distribution board to the outlets or equipment.

The IEC and US figures are set up differently. Compare them side by side below.

ReferenceTypical figuresStatus
Japan: JEAC 8001 (Naisen Kitei) Section 1310Feeder ≤2% and branch circuit ≤2% (up to 60 m, utility low-voltage supply); relaxed for longer runs as in the table abovePrivate code of the Japan Electric Association; widely used for design in Japan
IEC 60364-5-52, Annex G (Table G.52.1)Supplied from the public LV network: 3% lighting, 5% other uses. Private LV supply: 6% lighting, 8% other uses. Main wiring over 100 m may add 0.005% per meter beyond 100 m, up to 0.5%Recommended values; national rules may differ. Do not apply to motor starting and similar transients
US: NEC 210.19(A) and 215.2(A)(1) informational notes (note numbering varies by edition)3% for the branch circuit to the farthest outlet; 5% combined for feeder and branch circuitInformational notes are not mandatory, unless the local authority having jurisdiction (AHJ) or the project spec makes them so

For short runs on a utility low-voltage supply, the Japanese 2% + 2% budget is tighter than the US 3%/5% guidance. The three references also use different base voltages and categories. If the equipment maker specifies a permissible voltage range, use whichever limit is stricter: the code value or the equipment requirement.

Cable Sizes: Japanese mm², IEC mm², and AWG

Japanese drawings use mm², but not the IEC series. Japanese CV cable follows a series such as 2, 3.5, 5.5, 8, 14, 22, 38, 60, and 100 mm². IEC 60228 uses 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, and 120 mm², and US drawings use AWG and kcmil.

The table lists the nearest sizes in each system. These are nearest sizes by area, not equivalents. A smaller substitute needs a fresh voltage drop and ampacity check.

Japanese size (mm²)Nearest IEC 60228 size at or above (mm²)Nearest AWG/kcmil (area in mm²)
22.514 AWG (2.08)
3.5412 AWG (3.31), smaller
5.5610 AWG (5.26), smaller
8108 AWG (8.37)
14166 AWG (13.3), smaller
22254 AWG (21.2), smaller
38502 AWG (33.6) or 1 AWG (42.4)
60701/0 AWG (53.5) or 2/0 AWG (67.4)
1001203/0 AWG (85.0) or 4/0 AWG (107)
AWG areas calculated from the AWG diameter formula. Japanese sizes from a 600 V CV cable catalog (JIS C 3605). Ampacity also depends on insulation, installation method, and ambient temperature.

Watch the rows marked "smaller." Replacing 14 mm² with 6 AWG, for example, reduces the copper area by about 5%, which raises the voltage drop by about the same proportion.

How a Japanese Sizing Sheet Is Usually Built

Workers pulling a power cable onto a wall-mounted cable tray

Japanese designers check cable size against both 許容電流 (kyoyo denryu, ampacity) and the allowable voltage drop. When you review their sheet, expect the voltage drop part to follow the four steps below.

Figure 7: The Four Steps in a Typical Japanese Voltage Drop Check

Current and the allowable drop come first; the minimum cross-section is worked back from them, then a standard size is chosen.

STEP 01Load currentFrom system, voltage, and load rating, including planned additions
STEP 02Allowable drop in voltsPercentage from route length and supply type × standard voltage
STEP 03Minimum cross-sectionThe simplified formula solved for A
STEP 04Standard size and cross-checkNext size up, then checked against ampacity and the breaker

Ampacity depends on installation method and ambient temperature, so it comes from the manufacturer's data for the specific cable.

  • Step 1, load current: For motors, the nameplate rated current. Where several loads share a feeder, the loads that run at the same time are added, and loads planned for the near future are often included.
  • Step 2, allowable drop in volts: The percentage from the JEAC 8001 table × the standard voltage. At 2%, that is 4 V on a 200 V branch circuit and 2 V on a 100 V circuit, so lower-voltage circuits get fewer volts.
  • Step 3, minimum cross-section: For three-phase 3-wire, A = 30.8 × L × I ÷ (1000 × e), with e from Step 2.
  • Step 4, standard size: The next standard size up from the series, then checked against ampacity and the upstream breaker rating. Voltage drop, ampacity, and protection must all be satisfied.

Worked Example: Three-Phase 200 V, 30 A, 50 m Motor Circuit

Take a branch circuit to a three-phase 200 V motor (load current 30 A) located 50 m (164 ft) from the distribution board. With a 2% branch-circuit limit, the allowable drop is 200 V × 2% = 4 V.

Figure 8: Worked Example, Three-Phase 200 V, 30 A, 50 m

Working back gives 11.6 mm², so the standard size chosen is 14 mm².

STEP 01-02Set the conditionsThree-phase 3-wire, 200 V, I = 30 A, L = 50 m. At 2%, e = 4 V
STEP 03Minimum cross-sectionA = 30.8 × 50 × 30 ÷ (1000 × 4) ≈ 11.6 mm²
STEP 04Check the standard size14 mm²: e = 30.8 × 50 × 30 ÷ (1000 × 14) ≈ 3.3 V (1.65%)
One size smaller, 8 mm², gives about 5.8 V (2.9%), above the 4 V limit. 14 mm² becomes the candidate, and the final choice depends on ampacity, installation conditions, and the breaker.

Simplified formula (power factor 1, no reactance). Motor power factor and starting current call for a check with the basic formula. Fictional example for illustration.

The same CV cable catalog lists the ampacity of 3-core 8 mm² as 54 A (installed in air in a covered trench, 40°C base ambient). So 8 mm² carries 30 A easily, yet it fails the voltage drop limit. Sizing on ampacity alone is how long circuits end up short of voltage.

For comparison, the same circuit can be recalculated with the US K-factor (12.9, at 75°C). It gives about 4.0 V (2.0%) for 14 mm² and about 4.2 V (2.1%) for 6 AWG. That is right at or just over the Japanese 2% figure, which shows how much the resistance basis matters.

Circuits at lower voltage, such as 100 V, are even more sensitive to length. A single-phase 100 V branch circuit carrying 15 A over 30 m drops about 8.0 V (8.0%) on 2 mm² and about 2.9 V (2.9%) on 5.5 mm². Even 8 mm² gives about 2.0 V, right at the 2% limit, so 14 mm² is needed for any margin.

Ways to Reduce Voltage Drop

Because voltage drop is current × resistance, every fix either lowers the resistance or lowers the current. The Ministry of Agriculture, Forestry and Fisheries reference lists larger conductors, adjusting the sending voltage, power factor correction, and changing the starting method.

Figure 9: Four Ways to Reduce Voltage Drop

Two lower the resistance, and two lower the current.

Use a larger cableThe most reliable fix. Costs more and needs larger conduit or tray space
Shorten the runPlace a distribution board near the loads and feed it with a feeder
Raise the voltageMoving to 400 V cuts current. A major change involving transformers and equipment
Reduce the currentPower factor correction cuts reactive current; the starting method limits inrush

Which option fits depends on run length, load type, and the scope of work.

On existing circuits, the options usually discussed first are one cable size up or a distribution board closer to the loads, subject to review by the responsible engineer. Running a large feeder close to the loads and keeping the small branch circuits short limits the drop for the same amount of copper.

For the same power, doubling the voltage halves the current and halves the drop in volts. Because the reference voltage is also doubled, the drop as a percentage falls to about one quarter, and the benefit grows with run length.

Moving to 400 V, however, changes the voltage rating of transformers, motors, and control equipment. It is usually considered for new installations or major upgrades.

Power factor correction capacitors are another way to reduce reactive current.

Checklist: Reviewing a Japanese Voltage Drop Calculation

Use the list below when a Japanese contractor or equipment supplier sends a cable schedule or voltage drop sheet. Each item points to a common source of disagreement.

  • Formula used: Simplified formula (35.6 / 30.8 / 17.8) or basic formula with R, X, and power factor? The simplified formula is a poor fit for large motor feeders.
  • Wiring system and coefficient: Does the coefficient match the system (2 for single-phase 2-wire, √3 for three-phase, 1 for line to neutral on single-phase 3-wire)?
  • Length: Is L the one-way route length (kocho)? A round-trip length doubles the result.
  • Conductor and temperature basis: Copper or aluminum? Is the resistance at 20°C or at operating temperature? Compare with the basis in your own method.
  • Base voltage: Is the percentage taken on 100 V, 200 V, 400 V, or your local nominal voltage (for example 230/400 V or 480 V)?
  • Limit applied: Is it JEAC 8001, IEC 60364-5-52, the NEC informational notes, or a project spec? Are feeder and branch circuit drops added together?
  • Motor starting: Is the starting dip checked separately from the steady-state drop? If starting current is ignored, control devices can reset every time the motor starts.
  • Later additions: Have loads been added since the cable was sized? Extra load on the original cable raises the current and the drop.
  • Cable sizes: Are Japanese sizes (3.5, 5.5, 8, 14, 22, 38 mm²) available locally? If not, is the substitute checked again, not just matched by name?
  • Ampacity and protection: Is the ampacity based on the actual cable, installation method, and ambient temperature, and is it coordinated with the breaker?
  • Equipment voltage range: Does the terminal voltage stay within what the equipment maker allows, including any supply voltage variation?

Questions to Ask the Japanese Side

When the sheet leaves something unclear, these questions usually get you the missing information quickly. They work for contractors, panel builders, and equipment suppliers.

  1. Which formula did you use for each circuit: the simplified formula or the basic formula with R, X, and power factor?
  2. Is L the one-way route length (kocho)? Where are the start and end points?
  3. What conductor resistance and temperature basis did you use, and from which cable catalog?
  4. Which allowable drop did you apply (JEAC 8001 Section 1310, a project specification, or another standard)? Is the percentage based on the standard voltage?
  5. How did you split the drop between feeder and branch circuit?
  6. Did you check the voltage dip during motor starting? What starting method and starting current did you assume?
  7. What voltage range does the equipment accept at its terminals?
  8. If we substitute local cable (IEC mm² or AWG), which size do you consider acceptable, and will you recheck it?

A short email in plain English works well. For example: "Please confirm the formula, the conductor resistance basis (°C), the allowable voltage drop (%) and its base voltage, and whether L is the one-way length for each circuit in your voltage drop sheet."

Where This Guide Does Not Apply

This guide explains how to read Japanese voltage drop calculations. It is not a design procedure, and it does not replace the codes or the engineer responsible for your installation.

  • Local codes decide: Outside Japan, the limits and methods in your national code, the AHJ, and the project specification take priority over JEAC 8001 values.
  • Edition and project differences: Check the current edition of JEAC 8001 and its notes. Some companies and projects use their own stricter limits.
  • Simplified formula limits: It ignores reactance and power factor and assumes a single load at the far end, balanced phases, and copper. Large feeders, motor circuits, aluminum conductors, and distributed loads need the full method.
  • Not covered: Starting dips in detail, harmonics, high-voltage circuits, and DC systems such as PV strings or battery systems.
  • Who signs off: Cable sizing for a real installation should be confirmed by a qualified electrical engineer using the manufacturer's data for the actual cable.

Frequently Asked Questions

What Does 30.8 Mean in a Japanese Voltage Drop Formula?

It is √3 × 17.8, where 17.8 Ω is the resistance of 1 km of 1 mm² copper at 97% conductivity. The formula e = 30.8 × L × I ÷ (1000 × A) gives the three-phase line-to-line drop in volts, with L as the one-way length in meters and A in mm².

Is Voltage Drop the Same as Power Loss?

No. Voltage drop is the voltage lost along the cable, and power loss is the power that turns into heat in the cable as a result. Considering resistance alone, the loss is current² × resistance, so doubling the current quadruples the loss.

Does Voltage Drop Matter on 24 V DC Control Circuits?

Yes. At lower voltages, the same drop in volts is a larger percentage of the supply. With long runs to sensors or relays, check that the terminal voltage stays within the device's operating range.

Can I Use the Same Simplified Formula for Aluminum Cable?

Not as is. The coefficients assume 97% conductivity copper. For aluminum conductors, use the conductor resistance from the manufacturer's data in the basic formula.

Can Measurement Replace the Calculation?

On an existing circuit, measuring the voltage at the supply end and at the load terminals at the same time, with the load running, shows the actual drop. Maximum load and starting conditions are hard to capture this way, so new or expanded circuits still need a calculation with margin.

Sources

Filed underDrawings & Specs

Found this useful? Share it

About the editor

MONOSCOPE EditorFOUNDER & EDITOR

Spent about ten years at a plant equipment maker and a plant engineering company, proposing, designing, and commissioning equipment, then moved into web marketing. Now a web consultant for B2B manufacturers, helping them explain their products and technology. Licensed in Japan as an Energy Manager and a Third-Class Chief Electrical Engineer.

Has run an engineering blog since 2017 (500+ articles) and a Japanese YouTube channel with about 20,000 subscribers. Each English guide is written from the Japanese shop-floor point of view and checked against the cited standards.

MoreRelated

More guides

All guides
Advertisement